Hangzhou PRI-SAFETY Fire Technology Co., Ltd. is known as one of the most professional manufacturers and suppliers of various safety products in China. If the automatic fire suppression systems for electrical cabinet fm200 fire system meets your requirement, welcome to buy quality equipment made in China here from our factory. Our factory will offer you one stop service and one year warranty.

Products Description
Background:
The characteristics of electrical fire hazards are the distribution, persistence and concealment of fire hazards. Due to the wide distribution of electrical systems and long-term continuous operation, electrical lines are usually laid in concealed places (such as ceilings, cable trenches), and are not easy to be detected by the fire alarm system at the initial stage of a fire, nor are they easy to observe with the naked eye.
The danger of electrical fire is also closely related to the electricity consumption. When the electricity load increases, it is easy to cause electrical fires due to overcurrent. The casualties, property losses and social shocks caused by the fire are huge. Electrical fires mainly occur in buildings, where people are close, evacuation is difficult, and smoke is not smoothly exhausted. It is very easy to cause serious accidents of mass death and injury.
Description:
PRI-SAFETY electric equipment fire suppression systems have been specifically designed to protect electric equipment and put out electric fires caused by leakage electric (class E fire) quickly andefficiently.
These self contained pneumatic systems require no external energy or power supply. Upon flame impingement or heat, thepressurized detection tubing will burst and activate the cylinder valve to open and release the extinguishing agent.
PRI-SAFETY electric equipment fire suppression systems are specifically designed to extinguish fires of electric panel, battery bay, control panel, electric equipment etc. It is developed to prevent damage of equipment, records, people and other assets that are vital to a business.
Advantages:
* Simple, high quality and well engineered system. Easy to install.
* Fast, automatic actuation.
* We use gas instead of water to put out the fire without causing damage.
* When a fire occurs, the system will first detect it and then feedback control the fire extinguishing system to turn on and extinguish the fire within serval seconds.
* Remaining operational during power interruption. There is no need for manual close fire fighting.
Working Principle & Specification
For FM200/HFC227ea Fire Suppression System For Electrical Cabinet, it has 2 types for Low Pressure FM-200 Automatic Fire Suppression System,
one is Direct type activated by detection tube/emergency button and spray FM-200 extinguishing agent from the blasr hole in detection tube,
another is indirect type activated by detection tube/emergency button and spary FM-200 extinguishing agent from the nozzles in SS discharge pipe.

For Direct Type Low Pressure Direct FM-200 Automatic Fire Suppression System:
Working Principle:
When there is a fire, and reach 140 degrees celsius, the tube will repture a hole, and the fire agent will discharge from this hole to extinguish fires within several seconds.
| Items No. | EFS-D01 | EFS-D02 | EFS-D03 | EFS-D04 | EFS-D06 |
| Agent Capacity(kg) | 1kg | 2kg | 3kg | 4kg | 6kg |
| Extinguishing Agent | HFC-227ea, HFC-263fa, FK-5112 | ||||
| Working Pressure (bar) | 14bar | 14bar | 14bar | 14bar | 14bar |
| Test Pressure(bar) | 27bar | 27bar | 27bar | 27bar | 27bar |
| Cylinder Material | ST12 or SS304 | ST12 or SS304 | ST12 or SS304 | ST12 or SS304 | ST12 or SS304 |
| Detection & Discharge Pipe Tube | φ6mm | ||||
| Activation Temperature Detection Tube (ºC) | 140ºC, | ||||

For Indirect Type of Low Pressure Direct FM-200 Automatic Fire Suppression System:
Working Principle:
When there is a fire, and reach 140 degrees celsius, the tube will repture a hole, then the pressure will release from the hole, and it will leads to activate the valve of the fire system to open, then the fire agent will discharge from discharge pipe to extinguish fires within several seconds
| Items No. | EFS-ID06 | EFS-ID09 | EFS-ID12 | EFS-ID18 | EFS-ID25 |
| Agent Capacity(kg) | 6kg | 9kg | 12kg | 18kg | 25kg |
| Extinguishing Agent | HFC-227ea, HFC-263fa, FK-5112 | ||||
| Working Pressure (bar) | 14bar | 14bar | 14bar | 14bar | 14bar |
| Test Pressure(bar) | 27bar | 27bar | 27bar | 27bar | 27bar |
| Cylinder Material | ST12 or SS304 | ST12 or SS304 | ST12 or SS304 | ST12 or SS304 | ST12 or SS304 |
| Detection & Discharge Pipe Tube | φ6mm | ||||
| Activation Temperature Detection Tube (ºC) | 140ºC | ||||
Application:

Packing and Shipping

Company Brief:
PRI-SAFETY FIRE TECHNOLOGY is stablished in 2005, is focused on Automatic Fire Suppression Systems and Fire Equipment R&D, Design and Manufacture.
The Main Products are On/Off Road Vehicles & Machines Automatic Fire Suppression system, HFC-227ea & FK-5112 Clean gas Fire Suppression systems, CAFS(Mobile Compressed Air Foam System), Water Mist Fire System, Foam Mist Fire System, Co2 Fire System, etc.
The Products and Fire Systems are used in Mining Industry, Forest Industry, Agriculture, Petrochemical, Transportation, Electricity Power, Industry, Construction and other fields.
PRI-SAFETY Has Professional Technology Team, Have Ability Supply Design, Solution, and Customization, For Special Project Requirement, and Technology Training & Instruction After Sales.
PRI-SAFETY Has the Certificates, ISO9001:2015, TUV CE0036, ECE R107, CCC, and So On. The Products Meet the International Standard of EN, NFPA, CNAS, ECE, etc.