Hangzhou PRI-SAFETY Fire Technology Co., Ltd. is known as one of the most professional manufacturers and suppliers of various safety products in China. If the hfc-227ea fm200 gas total flood fire extinguishing system meets your requirement, welcome to buy quality equipment made in China here from our factory. Our factory will offer you one stop service and one year warranty.
HFC-227ea FM200 Gas Total Flood Fire Extinguishing System


Description:
When the control mode selection key on the automatic fire alarm and fire extinguishing controller is set to the "auto" position, the fire extinguishing system is under automatic control. When a fire occurs in the protection area, the temperature and smoke detectors will send out a fire signal through the automatic fire alarm and extinguishing control After the logic analysis of the device, it sends out a combined sound and light alarm signal, and sends out a linkage command at the same time to close the linkage device. After a delay, a fire extinguishing command is issued, the starting valve is opened to release the starting gas, and the starting gas is opened through the control gas pipeline valves and container valves release the fire extinguishing agent and implement fire extinguishing.
Advantages:
Very swift fire suppression. Reach extinguishing level ≤10s.
Safe to people. People is safe when exposed at the FM200 gas discharge level.
Low extinguishing concentration. Nearly no obscure to vision in person evacuation.
Easy to clean. No residue left, and minimize damage to sensitive equipment.
Environment friendly. Zero ozone depletion potential and zero global warming potential.
Simple installation, with small storage space.
Specification:
No. | Specification | Technical Parameter | |
1 | Filling pressure | 4.2Mpa | 5.6Mpa |
2 | Scale of Protective region for one zone | Area:max single-zone is 800m² volume:max single-zone is 3600m³ | |
3 | Spraying time | 10s | |
4 | Filling density | ≤950kg/m3 | ≤1080kg/m3 |
5 | Power | DC24V/1.6A | |
6 | Nitrogen Pressure of Driving Device | 6.0±1.0Mpa(20℃) | |
7 | Condition of reserving room for container | temperature: -10~50℃, relative humidity: ≤97% | |
8 | Max working pressure | 5.3Mpa | 8.0Mpa |
9 | Min working pressure | 4.2Mpa | 4.6Mpa |
10 | Capacity | 90L, 120L, 150L, 180L | |


HFC-227ea FM200 Gas Total Flood Fire Extinguishing System are generally used in conjunction with fire detectors, fire alarm fire extinguishing controllers, emergency start/stop buttons, sound and light alarms, deflation indicators and other fire fighting equipment. When a fire occurs in the protection area, the temperature and smoke detectors will send out a fire signal. After the logic analysis of the automatic fire alarm and extinguishing controller, it will send out a sound and light composite alarm signal, and at the same time send out a linkage command to turn off the linkage equipment. After a delay time, a fire extinguishing command is issued, the solenoid valve driver is opened, the container valve is opened, the fire extinguishing agent is released, and the fire is extinguished; if the duty officer discovers a fire, he can press the emergency start button outside the protective area door to implement the fire extinguishing operation ; There is also a manual button on the solenoid valve driver, and mechanical emergency manual operation can also be used to extinguish fire in an emergency.