Hangzhou PRI-SAFETY Fire Technology Co., Ltd. is known as one of the most professional manufacturers and suppliers of various safety products in China. If the pri-safety fm200 total flooding fire system meets your requirement, welcome to buy quality equipment made in China here from our factory. Our factory will offer you one stop service and one year warranty.

Products Description
FM200, also known as HFC-227ea, is a clean gaseous fire suppression agent commonly used in total flooding fire protection systems. The FM200 system is designed to extinguish fires by rapidly reducing the oxygen concentration within a protected space, thereby suppressing the combustion process. This type of fire suppression system is typically employed in areas where water-based systems might be ineffective or where the use of water could cause damage to sensitive equipment or valuable assets.




Products Specification
| No. | Specificaitons | Technical Parameter | |
| 1 | Filling Pressure | 4.2Mpa | 5.6Mpa |
| 2 | Spray Time | 10s | |
| 3 | Cylinder Material | Stainless Steel SUS304 | |
| 4 | Cylinder Head Size | G1" / G2" | |
| 5 | Filling density | ≤950kg/m3 | ≤1080kg/m3 |
| 6 | Max working pressure | 5.3Mpa | 8.0Mpa |
| 7 | Cylinder Capacity | 70L, 90L, 120L, 150L, 180L, 250L, 345L | |
| 8 | Condition of reserving room for container | Temperature: -10~50ºC, Relative humidity: ≤97% |
|
| 9 | Nitrogen Pressure of Driving Device | 6.0±1.0Mpa(20ºC) | |
| 10 | Valve Material | Stainless Steel SUS304 | |
| 11 | Power | DC24V/1.6A | |
| 12 | Scale of Protective region for one zone |
Area:max single-zone is 800m² volume:max single-zone is 3600m³ |
|
Working Type


Cylinder Specification

Fm200 Cylinder Specification---4.2MPa:
| Item | Capacity(L) | Inner Dia.(mm) | Height(mm) | Wall Thickness(mm) | Max. Working Pressure (Bar) |
| 1 | 32L | 300 | 620 | 4 | 4.2 |
| 2 | 90L | 350 | 1125 | 4.5 | 4.2 |
| 3 | 120L | 350 | 1430 | 4.5 | 4.2 |
| 4 | 180L | 400 | 1635 | 5.5 | 4.2 |
| 5 | 250L | 500 | 1500 | 8 | 4.2 |
Fm200 Cylinder Specification---5.6MPa:
(Just Listed some bottle specifications for reference)
| Item | Capacity(L) | Inner Dia.(mm) | Height(mm) | Wall Thickness(mm) | Max. Working Pressure (Bar) |
| 1 | 40L | 300 | 747 | 5 | 5.6 |
| 2 | 90L | 350 | 1125 | 6 | 5.6 |
| 3 | 120L | 350 | 1430 | 6 | 5.6 |
| 4 | 180L | 400 | 1635 | 7 | 5.6 |
| 5 | 250L | 500 | 1500 | 9 | 5.6 |
Accessories Specification
1.Normal Quality Valve

| Item | DN32 | DN40 | DN50 |
| Code NO. |
V32/4.2-PRI V32/5.3-PRI |
V40/4.2-PRI V40/5.3-PRI |
V50/4.2-PRI V50/5.3-PRI |
| Neck Thread | PZ56 | M64X2 | M80X2 |
| Actuator Thread | M18X1.5 | M18X1.5 | M18X1.5 |
| Diptube Thread | RC 1-1/4'' | RC 1-1/2'' | RC 2'' |
| High Pressure flexible thread | M48X2 | M56X2 | M68X2 |
| Pressure gauge thread | M10x1 | M10x1 | M10x1 |
| Working Pressure | 4.2Mpa/5.3Mpa | 4.2Mpa/5.3Mpa | 4.2Mpa/5.3Mpa |
| Applicable cylinder | <=100L | 120L 150L | 180L 250L |
2.High Quality Valve

|
Code NO.
|
AV25/4.2-PRI AV25/5.3-PRI |
AV50/4.2-PRI AV50/5.3-PRI |
|
| Size | G 1" | G 2" | |
| Nech Thread | 2-8UN.2A | 3 1/4-8UN.2A | |
| Nech Thread | G 1" | G 2" | |
| High Pressure Flexible Hose Thread | G 1" | G 2" | |
| Pressure Guage Thread | 1/8" NPT | 1/8" NPT | |
| Working Pressure | 6.7MPa | 6.7MPa | |
| Testing Pressure | 10.05MPa | 10.05MPa | |
|
<70L | 70L 90L 120L 150L 180L |
3.Normal Pneumatic and Soleniod Valve Paremeters

|
Pneumatic Valve (Normal Type) |
|
|
Code NO. |
PV-PRI |
|
Thread |
M16x1.5 |
|
Working Pressure |
6.6MPa |
|
Solenoid Valve (Normal Type) |
|
|
Code NO. |
SV90N-PRI |
|
Thread |
M18x1.5 |
|
Power |
DC 24V |
|
Drive Force |
90N |
3.Nozzles

|
Item |
DN25 |
DN32 |
DN40 |
DN50 |
|
Code.No |
N25-PRI |
N32-PRI |
N40-PRI |
N50-PRI |
|
Thread |
RC 1'' |
RC 1''-1/4'' |
RC 1''-1/2'' |
RC 2'' |
|
Material |
Brass |
|||
4.Control Panel Components:
The control panel for an FM200 total flooding system is a critical component that monitors, controls, and coordinates the various elements of the fire suppression system.
The components are as followings:

Products Application
The Stainless Steel Cylinder FM200 Total Flooding Fire System is designed for fire protection in various applications, especially in environments where the use of water-based systems is not suitable or could cause damage to sensitive equipment. The use of stainless steel cylinders is beneficial in areas where corrosion resistance and durability are essential. Here are some common applications of the Stainless Steel Cylinder FM200 Total Flooding Fire System:
Data Centers and Server Rooms:
Data centers house critical and sensitive electronic equipment, including servers and networking infrastructure. The FM200 system is well-suited for these environments as it provides rapid fire suppression without causing damage to the electronic components.


Telecommunication Facilities:
Facilities with communication equipment, such as telecommunication rooms and facilities housing switching equipment, benefit from the use of FM200 systems. The clean agent extinguishes fires without leaving residue that could harm sensitive telecommunications equipmen
Control Rooms:
Control rooms in various industries, such as manufacturing, energy, and transportation, often contain valuable and critical control systems. The FM200 system can protect these spaces without causing damage to control panels, displays, and other equipment.


Server Farms and IT Facilities:
Large-scale IT facilities, including server farms and IT infrastructure rooms, can utilize FM200 systems to protect against fires without the need for water-based systems that could damage the equipment.
Products Process

Packing & Shipping


Company Profile
PRI-SAFETY factory was built in 2005, is a national high-tech enterprise focusing on the research, design and manufacture of automatic fire suppression systems and fire fighting equipment.
And the main products we produce include : Vehicle and Mechanical Equipment Automatic Fire Suppression System, Kitchen Fire System, Heptafluoropropane Gas Fire Suppression System, FM200/FK-5112 Tool Flooding System, Water Mist Fire System, Compressed Air Foam Equipment(CAFS), Fire Trace Fire system, etc
We not only produce fire system but also design them and provide various fire solution, we have a professional technical team to help us with that, and also perfect aftersale-service.
Any question, like installlation, feel free to contact us, we are always online. And we has passed ISO9001:2015 quality management system certification, and its has CE and EN
certification, UN ECE R107 certificate for vehicle safety.
Our address