Fire Extinguishers Must Be Scrapped If One Of The Following

May 19, 2017

Leave a message

1. The cylinder body presses the water pressure test, the unqualified must scrap, does not permit the repair welding;

2. Serious corrosion of the cylinder (large area of patent leather, rust area is greater than, equal to One-third of the total area of the cylinder) or connecting parts, the bottom of the tube is seriously corroded;

3. The inner fastener head does not have (or not installed) the gas discharging screw and the fixing screw;

4. handwheel-type valve carbon dioxide fire extinguisher, must replace the pressure valve;

5. Fire extinguisher quantity is greater than or equal to 4 Shan, should be replaced with intermittent injection mechanism of the head or add spray gun, can not be replaced should be scrapped.

6. The cylinder body is badly deformed;

7. Unreasonable structure (such as cylinder flat bottom, gas cylinder external, inlet pipe from the cylinder into the cylinder inside the dry powder fire extinguisher);

8. No factory name and factory year (including decals fall off, or although there is decals, but has not seen the factory name and factory years);

9. Manufacturers who have not obtained the production license; [3]

10. The Ministry of Public Security or the provincial (city, district) Fire Department orders prohibit sale and maintenance.